USI GAS DETECTORS
Scroll down this page for details on the following:
PORTABLE GAS DETECTOR
WALL-MOUNT GAS DETECTOR / MONITOR
SINGLE AND MULTI-CHANNEL GAS DETECTOR / MONITOR IN NEMA-4 ENCLOSURE
SENSOR DATA TRANSMITTER (SDT) GAS DETECTOR
|
|
PORTABLE GAS DETECTOR
The portable toxic gas or combustible gases detector with audiol/visual alarms and meter display is ideal for confined space monitoring. The detector is compact, light weight, and battery operated. With built-in charger and Ni-Cad batteries allows the unit 10 hours of continuous operation. The hand held probe with the sensor (no mechanical pump) and 5 feet of wire provides local area gas measuring. Analog meter, or 4-digit large LCD digital display indicates PPM or % LEL. Shoulder held carrying case and instrument case are also included. 0-1 VDC output for data acquisition is optional.
FEATURES
-
Rugged, compact, lightweight with shoulder carrying case and instrument case
-
Uses a UL approved solid state sensor with 1 year warranty (estimated life over 10 years)
-
Audio/visual alarms
-
Low battery warning light
-
Accurate Analog or Digital reading for PPM or %LEL
-
Rechargeable Ni/Cad Battery and built in battery charger
-
Fast warm up time 3-4 minutes and response time
-
Sensor high poison resistant to sulphur, lead, silicone and halogenated compounds
-
115, or 220 V AC line charge
SPECIFICATIONS - CONTROLLER
| Dimensions: |
8"H x 5"W x 3"D |
| Operating Temp: |
-10°F to +150°F |
| Meter Display: |
Analog PPM, or % LEL, or Optional 4 digits LCD indicates PPM or % LEL |
| Power: |
3.6V DC Ni-Cad battery |
| Power Usage: |
2.0 watt maximum |
| Operating Hours: |
10 hours continuous (minimum) |
| Battery Signal: |
Visual Yellow LED indicates Low battery |
| Battery Charger: |
Built in charger, 115VAC or Optional 220 VAC |
| Panel Control: |
Zero and Span adjustments |
| Alarms: |
Visual Red LED, Audio buzzer 75 dB |
| Panel Indicators: |
Power On (Green LED), In-Charge (Orange LED) |
| Weight: |
2.0 Ibs. (13 Ibs. in case) |
|
|
WALL-MOUNT GAS DETECTOR / MONITOR
The wall-mount toxic gas or combustible gases detector with audio/visual alarms and relay contacts provides continuous open/enclose space monitoring. The basic unit has a detecting sensor and controller joining together. If necessary, remote sensor with explosion-proof junction box housing and 50 feet cable wire (longer length can be extended to 600 feet) connection are also available. The explosion proof sensor and housing are ideal for hazardous area monitoring and meet NEC requirements for Class I, Division I, Group A-B-C-D. All the models can provide either 4-20mA or 0-1 VDC output for data acquisition purpose, and PLC interfacing. Analog Meter indicates PPM or % LEL. Digital display use large Red LED is also available.
FEATURES
- Continuous 24 hour monitoring
- Compact, and durable unit
- Explosion proof housing for remote sensor
- Audio/visual alarms and relay contacts
- Malfunction alarm and Test/Checking alarm set switches
- Infrequent maintenance and calibration required
- Remote sensor reliable to 600 feet from controller
- Solid-State (PPM), Catalytic (%LEL) sensors, fast warm-up time
- Optional recorder terminals
SPECIFICATIONS - CONTROLLER
| Dimensions: |
8"Hx 5"W x 4"D |
| Readout Meter: |
Analog PPM, % LEL, or 4 Digits big 0.3" red LED |
| Temperature Range: |
-10°F to +150°F |
| Repeatability: |
+ or - 2% |
| Power Usage: |
~3.5 watts |
| Power Input: |
Standard 115VAC, or 220 VAC, or 24 VDC |
| Alarms Circuits: |
Fail LED (yellow), Alarm LED (red), Audio sound (steady) |
| Alarm Point: |
Variable setting in the meter range |
| Panel Controls: |
Zero, Span, Set "alarm", Test and alarm set Check switches |
| Relay Contacts: |
SPDT 1 A, 115 VAC or 24 VDC |
| Analog Output: |
(Optional) 4-20mA or 0-1 VDC |
| Weight: |
5lbs (sensor attached to controller type), 9lbs (remote sensor type) |
|
|
FOR TWO-STAGE ALARMS - CONTROLLER
| Audio Alarms: |
Low (pulse tone), High (steady tone) |
| |
|
Panel Light Indicators:
|
Power ON (green LED) Fail alarm (orange LED) Low alarm (yellow LED flashing) High alarm (red LED continuous)
|
| |
|
Panel Controllers:
|
Zero, Span, Low & High alarm Set points Low & High alarm settings Check switches Reset (Latching or Non-latching at high alarm), Test Switch
|
| |
|
Relay Controllers:
|
Fail Relay Low Relay High Relay (NO, COM, NC 1A 115 VAC, or 1A 24 VDC)
|
|
SINGLE AND MULTI-CHANNEL GAS MONITOR/ALARM IN NEMA-4 ENCLOSURE
The gas monitor includes remote sensor(s) and controller in NEMA-4 enclosure for indoor, or outdoor installation. Each sensor with explosion-proof junction box housing and 50 feet cable wire connects to the controller. Each channel operates independently and indicates the concerned gas level at differnt sites and can be seen instantly. Standard individual channel has Power GREEN LED, Alarm RED LED, Fail (Malfunction) YELLOW LED, and Meter display (PPM or % LEL). Basic unit has individual module, master module, and power module. This design gives easy operation and replacement, if necessary.
SPECIFICATIONS - CONTROLLER
| Temperature Range: |
-10°F to +150°F (-20°C to 65°C) |
| Repeatability: |
±2% |
| Meter Range: |
PPM or % LEL |
| Alarm Circuit: |
Fail, Alarm |
| Audio Alarm Outputs: |
95 dB (steady tone) |
| LED Indicators: |
Power LED (Green), Fail LED (Yellow), Alarm LED (Red) |
| Panel Controls: |
Zero, Span, Alarm Set point, Alarm Set Check switch, Test switch, Reset switch (non-latch mode) |
| Power Input: |
115 VAC/220VAC 50/60Hz, or 24 VDC |
| Power Consumption: |
~3.5 watts per channel |
Dimensions:
|
9"W x 12"H x 5"D (1 Channel) 12"W x 16"H x 8"D (2 Channel) 16"W x 16"H x 8"D (4 Channel) 20"W x 16"H x 8"D (8 Channel) 24"W x 20"H x 8"D (10 Channel) |
Weight:
|
12 Lbs. - 1 Channel 24 Lbs. - 2 Channel 30 Lbs. - 4 Channel 40 Lbs. - 8 Channel 50 Lbs. - 10 Channel |
| Panel Box: |
NEMA type 4 panel enclosure, UL listed |
| Cable Length: |
#22 or #20 AWG Shield, 3 conductor cable, up to 600 feet or longer |
| Warranty: |
1 year |
| Recorder Output (optional): |
4-20mA (500Ω Load max.), or 0-1 VDC |
Relay Contacts (Individual channel): |
Fail Relay, Alarm Relay (NO, COM, NC 1A 1 - 115VAC, or 1A - 24VDC) |
Common Relay (2 channel or more system only): |
(NO, COM, NC 7A - 115VAC, 220 VAC, or 7A- 24 VDC) |
* System includes NEMA 4 enclosure and remote sensor with 50 feet cable.
|
FOR TWO-STAGE ALARMS IN SINGLE AND MULTI-CHANNEL UNIT - CONTROLLER
| Audio Alarms: |
Low (pulse tone), High (steady tone) |
| Panel Light Indicators: |
Power ON (green LED) Fail alarm (orange LED) Low alarm (yellow LED flashing) High alarm (red LED continuous) |
| Panel Controllers: |
Zero, Span, Low & High alarm Set points, Low & High alarm settings Check switch Reset (Latching or Non-latching at high alarm), Test switch |
| Relay Contacts (Individual channel): |
Fail Relay, Low Relay, High Relay (NO, COM, NC 1A - 115VAC, or 1A - 24 VDC) |
Common Relay (2 channel or more system only): |
(NO, COM, NC 7A - 115VAC, 220 VAC, or 7A - 24 VDC) |
|
|
|
|
|
|
SENSOR DATA TRANSMITTER (SDT) GAS DETECTOR
The Sensor Data Transmitter (SDT) detects the toxic gas, or combustible gases and indicates the concerned gas level with 4-digits Red LED PPM or % LEL. The SDT stands alone monitoring the dangerous gases/vapors with explosion-proof sensor and housing. The housing has a glass window, which you can see through the bright red digits in dark or light areas. The unit provides linear 4-20mA output for data logger and recorder. the SDT operates on 12 VDC power supply. It's also available for 24 VDC or 115/220VAC power. It can be installed at hazardous areas and meets NEC requirements for Class I, Division I, Group B, C, D.
SPECIFICATIONS
| Dimensions: |
4.5"Dia. x 4"D |
| Storage Temperature: |
-10°F to +150°F (-20°C to +65°C) |
| Power: |
12 VDC (Optional 24 VDC, 115/220VAC) |
| Power Usage: |
3.5 watts maximum |
| Panel Controls: |
Zero, Span (Optional relay switch for preset alarm, 7A - NO, COM, NC) |
| Display: |
0.3" red LED of PPM or % LEL (4 digits) |
| Weight: |
3.5 lbs. |
|
|